AgControlli
AGL200 Single-Phase DIN-Rail Energy Meter
AGL200 kWh Meters

Single-Phase DIN-Rail Energy Meter

Compact 2-module Class 1 single-phase kWh meter, 10(80) A direct connection, RS-485 Modbus RTU

Modbus RTU Pulse

Features

  • Two DIN modules — fits the gap in any final-circuit distribution board
  • Direct 80 A connection — no current transformer for single circuits
  • Modbus RTU on the same pair as the rest of the sub-metering bus
  • Pulse output for controllers without a serial port
Enquire about this product

No forms — email directly to sales@agcontrolli.com

Technical support included

Specifications

Phases Single-phase 2-wire
Voltage Input 220 V AC, 50 Hz
Current Input 10(80) A direct connection, starting current 40 mA
Measurements U, I, P, Q, S, PF, F
Accuracy Class Class 1 active energy (IEC 62053-21)
Energy Registers Forward and reverse active kWh, 000000.00–99999999 kWh; 3-month frozen history
Output Signal RS-485 Modbus RTU (address 1–254, 1200–19200 bps), active pulse output 1000 imp/kWh
Display 8-digit LCD, 3-key programming
Tariffs Optional multi-tariff: 4 time zones, 4 tariff rates
Housing 2-module DIN rail, 90 × 36 × 65 mm
Ambient Temperature -25 to +55°C, ≤ 95% RH non-condensing, altitude < 2000 m
Certifications Manufacturer states MID (Class B), IEC 62053-21 / -22

Applications

  • Tenant and apartment sub-metering
  • Individual circuit metering in distribution boards
  • Telecom tower, shop and small-office sub-metering
  • Lighting, socket and small-plant consumption tracking

System integration

Works with any BMS or controller that accepts Modbus RTU / Pulse signals.

Ready to specify?

Send us your circuit type, current, communication and quantity — we'll confirm availability and lead time.

sales@agcontrolli.com