AG-GDC-100 Flammable Gas Detectors
Fixed Combustible Gas Detector
Explosion-proof catalytic bead detector for methane and combustible gases, 0–100 % LEL
4–20 mA Modbus RTU
Features
- Detects at high level for lighter-than-air gases — mount above the leak source
- Two field-adjustable alarm stages drive ventilation boost and gas shut-off independently
- Reports directly to BMS or PLC — no dedicated gas panel required
- Catalytic sensors require scheduled bump testing and calibration to remain reliable
Enquire about this product
No forms — email directly to sales@agcontrolli.com
24-month warranty · Technical support included
Specifications
| Target Gas | Methane (CH₄) / natural gas; other combustible gases on request |
| Measuring Range | 0–100 % LEL |
| Resolution | 1 % LEL |
| Sensor Technology | Catalytic combustion (pellistor) |
| Alarm Stages | Two, field-adjustable (typically set 20 % / 40 % LEL) |
| Output Signal | 4–20 mA and RS-485 Modbus RTU — confirm configuration at order |
| Supply Voltage | 24 V DC |
| Response Time | ≤ 30 s (T90) |
| Ambient Temperature | −20 to +60°C |
| Humidity | 15–90 % RH, non-condensing |
| Explosion Protection | Ex d IIC T6 |
| Cable Run | Up to 1000 m |
| Display | LCD showing live concentration |
| Certifications | Manufacturer states CE, ATEX |
Applications
- Gas engine and generator halls
- Gas pressure reduction and metering skids
- Boiler houses and fuel gas trains
- Plant rooms with piped natural gas
Compatible Platforms
Reliable Controls MACH-ProSysSiemens Desigo CCHoneywell EBISchneider EcoStruxureJohnson Controls Metasys
Works with any BMS that accepts 4–20 mA / Modbus RTU signals.
Other Gas Detection
AG-GDT-300
Fixed Carbon Monoxide Detector
Explosion-proof electrochemical CO detector for occupied plant rooms, 0–1000 ppm
4–20 mAModbus RTU
AG-GDO-400 Fixed Oxygen Deficiency Monitor
Oxygen depletion and enrichment monitoring where nitrogen, argon or CO₂ is stored, 0–30 % vol
4–20 mAModbus RTU
AG-GDC-150 Fixed Hydrogen Detector
Catalytic bead hydrogen detection for battery rooms and electrolyser areas
4–20 mAModbus RTU
Ready to specify?
Send us your pipe size, media, range and protocol — we'll confirm availability and lead time.
sales@agcontrolli.com